6.7.1.3. Preparing cables for cable entries with sealing modules
Prepare cables with an outer cable screen or shield for EMC bonding with the metal enclosure
of the cabinet as illustrated. Install the sealing modules according to the instructions of the
sealing module supplier.
NOTICE
Risk of cable damage! Incorrectly connected pigtails (10, Fig. 66) can create unwanted current
loops that can damage the cables.
→ Connect each pigtail directly to the PE busbar.
→ DO NOT shorten or connect the pigtails to each other (see Section 6.4, "Grounding",
page 86)
1
2
3
4
5
6
Key:
(1)
Sealing module
(2)
Frame
(3)
Conductive foil of sealing module
(4)
Cable clamp
(5)
Shrinkable sheath seal
(6)
Heat-shrinkable termination
(7)
Outer cable sheath
(8)
Cable sheath removed to expose cable
shield/armor
Fig. 66. Preparing power cables for sealing modules
PRODUCT
ACS5000W gen. 2
7
8
9
10
11
DOCUMENT KIND
User manual
12
10
(9)
Shield extension to be connected to PE busbar
(not applicable if the cable only has armor)
(10) Cable screen extension to be connected to the
PE busbar
(11) Cable lug as specified by the cable supplier
and suitable for M12 bolt
(12) Sheath seal
DOCUMENT ID.
3BHS799208 E01
ELECTRICAL INSTALLATION
REV.
LANG.
PAGE
J
en
101/186