Fig. 77. Cable Routing In Cou Cabinet - ABB ACS5000 User Manual

Water-cooled (generation 2)
Hide thumbs Also See for ACS5000:
Table of Contents

Advertisement

Fig. 77. Cable routing in COU cabinet

6.8.2.2.2. Control power supply
Connect the cable for the control power to terminal X2 (11, Fig. 76).
6.8.2.2.3. Control signals
Connect the cables to the following terminals:
X10, X11 (10, Fig. 76) Main circuit breaker signals and emergency off signals
X20 to X27 (7, Fig. 76) Control signals of monitored equipment
6.8.2.2.4. Fieldbus interface
Connect the cable directly to the fieldbus adapter.
6.8.2.2.5. Encoder interface
1. Connect the cable directly to the encoder adapter.
2. Connect the overall shield and the individual shields of the encoder cable to the
copper busbar.
NOTICE DO NOT connect the shields directly to the encoder adapter.
PRODUCT
ACS5000W gen. 2
1
2
DOCUMENT KIND
User manual
Key:
(1)
Top cable entry
(2)
Bottom cable entry
DOCUMENT ID.
3BHS799208 E01
ELECTRICAL INSTALLATION
REV.
LANG.
PAGE
J
en
112/186