8.8.1. Checks before starting the drive
When the drive is put into service after it has been commissioned, or after it has been taken out
of service for a longer period, check the drive according to the following list:
–
Tools and foreign objects are not in the cabinet.
–
All auxiliary power supplies from external sources are switched on.
–
All internal circuit breakers of the drive have been closed.
–
All covers have been fitted.
–
All locking screws have been removed from the locking bars on the inside of the doors of
medium voltage compartments.
–
All doors have been closed and locked or bolted.
–
Grounding switch is in the not grounded position.
–
MCB is in operating position.
–
Run interlock is not active.
8.8.2. Starting the drive remotely
When the drive system is operated from a higher-level control system or an operator control
desk, follow the instructions in the applicable manuals.
8.8.3. Starting the drive locally
1. Set the CDP control panel to local control mode.
2. If the EMERGENCY-OFF RESET push button is flashing, press the push button to
cancel flashing.
Each time the auxiliary voltage is switched off and on again, the emergency-off safety relay
of the drive is actuated and lets the EMERGENCY-OFF RESET push button flash.
The push button also flashes if the EMERGENCY-OFF push button on the control
compartment door, or any other emergency-off switch linked to the drive, is pressed. If the
push button continuous flashing, verify that there is no emergency-off command active.
For more information, see Section 8.9.1, "Stopping the drive in an emergency", page 133.