5.10.3. Installing IP54 roof-mounted cooling units

CAUTION
Heavy object! An IP54 cooling unit weighs 98 kg.
98 kg
→ Only use the rotating eyebolts (ABB ID: 3BHE015753P0008) that were delivered with
the loose part of the drive
→ Use appropriate slings and shackles with the eyebolts
→ Before you begin, read Section 4.5.3, "Lifting with rotating eyebolts", page 61

TABLE 6 Installation material per IP54 unit

Item
Self-tapping Torx screws
Washers with sealing
Tube spacers
1. Install rotating eyebolts in the top corners of the IP54cooling unit.
CAUTION! For a single lifting operation, tighten the eyebolts (1, Fig. 42) firmly with the star
key (2, Fig. 42). DO NOT leave the star key in the bolt head. The eyebolt must be able to rotate
360° freely. For a permanent installation, tighten the eyebolts to the nominal torque that is
specified in Section 4.5.1, "Lifting attachment types", page 59.
1
4 ×
2
3BHE015753P0008

Fig. 42. Lifting an IP54 cooling unit

2. Attach the appropriate slings and shackles to the eyebolts.
3. Orient the eyebolts in the direction of force.
CAUTION! Rotation during transportation must be avoided.
PRODUCT
ACS5000W gen. 2
Quantity
Details
22
M6 × 16
22
6.8 × 1 (4.8 × 2.8)
2
1
360°
DOCUMENT KIND
User manual
1
1
DOCUMENT ID.
3BHS799208 E01
MECHANICAL INSTALLATION
ID number
HAQN401050P0259
3BHB034338R0001
1
4
5
3
REV.
LANG.
PAGE
J
en
76/186