9. Priority Setting

You can only set the operation mode and unit temperature setpoint from one specific controller (the main
controller) in the same refrigerant system without having to use the central controller. The operation of sub
controller is decided by the priority setting and power saving details setting of the main controller.
Example
Controller A
(Main)
Without Priority
Operation Mode
With Priority
Operation Mode + Temperature Setpoint
Selection Possible
:
▲: Selection Possible Partially
- Operation Mode + FAN set by Controller A (Main)
- Only when COOL mode COOL↔DRY
×
: Selection not possible (Apply to setting temperature of Controller A (Main))
NOTES:
This controller comes normally pre-set with factory-supplied default settings. It is possible to set, depending
on what is pre-set in the priority settings of the Test Run menu.
Only the temperature setting cannot be set as priority. Also, even if operation mode is set as priority, in the
case of COOL/HEAT Automatic Mode, the priority is temporarily overridden.
It is not possible to set the "Cool/Heat Auto Changeover" and "Priority Setting" at the same time. In addition,
the priority will be removed once the "Cool/Heat Auto Changeover" takes effect.
When using two controllers, it is not possible to set priority.
If one of the devices in the same refrigerant cycle is connected, the main function cannot be used.
○ Outdoor unit or Indoor unit power saving capabilities are not available
○ Receiver Kit
○ Central Controller
○ Advanced Wired Remote Controller and Wired Remote Controller are set "ON" with the selected operation
mode, setting adjustment of Temperature Setpoint, and setting adjustment for cooling
○ Cooling/Heating Changeover Switch Unit
1.
Set Operation Mode and Temperature Priority
Step1. Select "Installation Menu" on the Service & Installation screen and press "OK".
Step2. Select "Priority Setting" and press "OK".
Step3. Press " " or " " to change in order the "No Setting" ↔ "Operation Mode" ↔ "Operation Mode + Set
Temp".
Select the setting and press "OK" to display the confirmation screen.
Step4. Press " " to return to the Installation Menu.
A16381TMF2
Controller B
(Sub)
Table E. List of operations that can be performed when priority is set
Priority Setting
Controller C
(Sub)
Controller A (Main)
Operation Mode
Temperature Setpoint
9. Priority Setting
Remote Selection
Controller B and C (Sub)
Operation
Temperature
Mode
Setpoint
×