16. Temperature Range Restriction

16. Temperature Range Restriction
The temperature range can be set by the wired remote controller.
1.
Set Temperature Range
Step1. Select "Service Menu" on the Service & Installation screen
and press "OK".
Step2. Select "Temperature Range Restriction" and press "OK".
Step3. Select "Lower Limit for Cooling Operation" or "Upper Limit
for Heating Operation" and press "OK".
Step4. Press " ", " ", " ", or " " to select the setting value.
Step5.
After value setting, select "
return to Step3.
NOTES:
Please make sure that the upper limit value is equal to or greater than the lower limit value.
Please make sure that the upper heating limit is set equal to or greater than the lower heating limit.
Different indoor and outdoor units have different temperature ranges.
When Cool/Heat Auto Changeover is effective, the upper and lower limit for auto heating/cooling is displayed
in "Temperature Range Restriction". Please set the upper limit greater than the lower limit.
When using two wired remote controllers, the auto upper and lower limit are not synchronized. Please set
them with the own wired remote controllers.
When Dual Setpoint is effective, the upper and lower limit for dual setpoint is displayed in "Temperature
Range Restriction". Please set the upper limit greater than the lower limit.
When using two wired remote controllers, the auto upper and lower limit are not synchronized. Please set
them with the own wired remote controllers. Please note that the temperature setting is "cooling setting
temperature ≥ heating setting temperature

17. Dual Setpoint Setting

The setting allows you set the temperature of cooling and heating individually.
To use this function, refer to the Item b8 (Page 10 ) to enable auto function in function selection.
1.
Set Dual Setpoint
Step1. Select "Service Menu" on the Service & Installation screen
and press "OK".
Step2. Select "Dual Setpoint" and press "OK".
Step3.
Press " " or " " to select "ON" or "OFF".
Step4. Press "OK" to confirm the setting.
Step5.
Press " " to return to Step2.

18. Main/Sub Display Setting

The main or sub display of the remote controller can be turned off.
1.
Set the main/sub display invisible.
Step1.
Select "Service Menu" on the Service & Installation screen
and press "OK".
Step2. Select "Main/Sub Display" and press "OK".
Step3.
Press " ", " ", " ", or " " to select "Not Display".
Step4. Press "OK" to confirm the setting.
Step5. Press " " to return to Step2.
34
" and press "OK". Press " " to
OK
o
o
+2
C(3
F)".
Upper/Lower Limit for Cooling
86°F
64°F
Upper Limit Lower Limit
Set the upper limit larger than the lower limit.
Dual Setpoint
OFF
ON
OK
Select
Conference Room
A/C
78
F
Sav: Low | Main
78
Temp
Cool
Fan Speed
Louver
With Priority Setting No Priority Setting
Main
No icon
Sub
OK
Back
Back
Menu
A16381TMF2

Advertisement

Table of Contents
loading

Table of Contents