Circuit breakers

The table below lists MCB circuit breakers that can be used with the drive.
Drive
MCBs
type
ABB type
ACS560-
3-phase U N = 380...480 V
02A6-4
S 203P-B/C/Z 10
03A3-4
S 203P-B/C/Z 10
04A0-4
S 203P-B/C/Z 10
05A6-4
S 203P-B/C/Z 10
07A2-4
S 203P-B/C/Z 10
09A4-4
S 203P-B/C/Z 10
12A6-4
S 203P-B/C/Z 16
017A-4
S 203P-B/C/Z 20
025A-4
S 203P-B/C/Z 25
033A-4
S 203P-B/C/Z 32
039A-4
S 203P-B/C/Z 40
046A-4
S 203P-B/C/Z 50
062A-4
S 803S-B/C 80
073A-4
S 803S-B/C 80
088A-4
S 803S-B/C 100
106A-4
S 803S-B/C 125
145A-4
XT4 L 250 Ekip
LS/I In=250 3p F
F
169A-4
XT4 L 250 Ekip
LS/I In=250 3p F
F
206A-4
T4 L 320
PR221DS-LS/I
In=320 3p F F
246A-4
T5 L 400
PR221DS-LS/I
In=400 3p F F
293A-4
T5 L 630
PR221DS-LS/I
In=630 3p F F
Max.
Tmax
short-cir-
frame XT
cuit
/ T class
I sc
kA
A
20
N/A
20
N/A
20
N/A
20
N/A
20
N/A
20
N/A
20
N/A
20
N/A
20
N/A
12
N/A
12
N/A
12
N/A
50
N/A
50
N/A
50
N/A
50
N/A
65
XT4
65
XT4
65
T4
65
T5
65
T5
Technical data 147
Tmax rat-
Electron-
ing
ic release
A
A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
250
250
250
250
320
320
400
400
630
630
3AXD10000561047.xls A
SACE ordering
code for breaker
and release unit
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1SDA068555R1
1SDA068555R1
1SDA054141R1
1SDA054365R1
1SDA054420R1