WARNING!
Do not connect the +24 V AC cable to the control board ground when the
108 Electrical installation
control board is powered using an external 24 V AC supply.

NPN configuration for digital inputs

NPN configuration for digital inputs
Internal and external +24 V power supply connections for NPN configuration are
Internal and external +24 V power supply connections for NPN configuration are
shown in the figure below.
shown in the figure below.
Internal +24 V power supply
NPN connection (sink)
X2 & X3
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
WARNING!
Do not connect the +24 V AC cable to the control board ground when the
WARNING!
Do not connect the +24 V AC cable to the control board ground when the
control board is powered using an external 24 V AC supply.
control board is powered using an external 24 V AC supply.
Connection for obtaining 0...10 V from analog output 2 (AO2)
To obtain 0...10 V from analog output AO2, connect a 500 ohm resistor (or two 1
kohm resistors in parallel) between the analog output 2 AO2 and analog common
ground AGND.
Examples are shown in the figure below.
External +24 V power supply
NPN connection (sink) )
X2 & X3
10 +24V
11 DGND
+ 24VDC
12 DCOM
0VDC
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6