Input Power Cable - ABB ACS560 Hardware Manual

0.75 to 160 kw, 1.0 to 215 hp
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

102 Electrical installation
Note: Frame R8 only:
If you connected the connector to only one conductor, ABB recommends to
put the conductor under the upper pressure plate.
The connectors are detachable, but ABB recommends not to detach them. If
you do, detach and reinstall the connectors as follows.

Input power cable

10. Connect the input power cable as in step 9.
M5×25/35
Frame size
L1, L2, L3, T1/U, T2/V, T3/W
R5
R6
R7
R8
Terminals T1/U, T2/V and T3/W
Remove the nut attached to the connector and its busbar.
Put the conductor under the connector pressure plate and pre-tighten the
conductor.
Put the connector back to its busbar. Start the nut, and turn it by hand to at
least two rotations.
WARNING!
Before using tools, make sure that the nut/screw is not cross-threaded.
Cross-threading damages the drive and causes danger.
9b
9a
8
N·m
lbf·ft
5.6
4.1
30
22.1
40
29.5
40
29.5
10b
10a
8
PE
N·m
lbf·ft
2.2
1.6
9.8
7.2
9.8
7.2
9.8
7.2
N·m
lbf·ft
1.2
0.9
1.2
0.9
1.2
0.9
1.2
0.9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents