Switches; Pnp Configuration For Digital Inputs - ABB ACS560 Hardware Manual

0.75 to 160 kw, 1.0 to 215 hp
Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

10)
Input signal
11)
Output signal

Switches

Switch
Description
S100
Modbus link termination and biasing
(TERM
voltages to the bus.
& BIAS)
Set to ON position when the drive is the
last unit on the link.
S100
Modbus link termination. Must be set to
(TERM)
the terminated (ON) position when the
drive is the first or last unit on the link.
S200
Switches on the biasing voltages to the
(BIAS)
bus. One (and only one) device, prefer-
ably at the end of the bus must have the
bias on.

PNP configuration for digital inputs

PNP configuration for digital inputs
Internal and external +24 V power supply connections for PNP configuration are
Internal and external +24 V power supply connections for PNP configuration are
shown in the figure below.
shown in the figure below.
Internal +24 V power supply
PNP connection (source)
X2 & X3
10 +24V
11 DGND
12 DCOM
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
WARNING!
Do not connect the +24 V AC cable to the control board ground when the
WARNING!
Do not connect the +24 V AC cable to the control board ground when the
control board is powered using an external 24 V AC supply.
control board is powered using an external 24 V AC supply.
NPN configuration for digital inputs
Internal and external +24 V power supply connections for NPN configuration are
shown in the figure below.
Internal +24 V power supply
Electrical installation 107
Position
Term & BIAS off
(default)
ON
1
Term & BIAS on
BUS not terminated (default)
ON
1
BUS terminated
BIAS off (default)
ON
1
BIAS on
Electrical installation 95
External +24 V power supply
PNP connection (source)
X2 & X3
10 +24V
11 DGND
0 V DC
12 DCOM
+24 V DC
13 DI1
14 DI2
15 DI3
16 DI4
17 DI5
18 DI6
External +24 V power supply