6.1.7. Object 0x6046: vl_velocity_min_max_amount

This object indicates the configured minimum and maximum amount of velocity (unit min
vl_velocity_max amount sub-object is mapped internally to the vl_velocity_max positive and vl_velocity_max
negative value. The vl_velocity_min amount sub-object is mapped internally to the vl_velocity_min positive
and vl_velocity_min negative value.
At initial configuration, the Upper limit frequency (ul) and Lower limit frequency (ll) of the drive may be
not same value with Object 0x6046 setting value. And when change the Upper limit frequency and the lower
limit frequency of the drive parameter, Object 0x6046 value is different with the drive parameters.
To correspond these limit value, set Object 0x6046. And if need, execute Store Parameters command
(Object 0x1010) to save the parameter to EEPROM.

6.1.8. Object 0x6048: vl_velocity_acceleration

This object indicates the configured delta speed and delta time of the slope of the acceleration ramp. Unit is
-1
min
.
[VF-S15]
Velocity acceleration delta speed : 225 to 30,000 min
Velocity acceleration delta time : 0 to 3,600 s
[VF-AS3]
Velocity acceleration delta speed : 225 to 32,700 min
Velocity acceleration delta time : 0 to 6,000 s
Note: Do not change the acceleration/deceleration time unit (parameter f519), if change the parameter,
the setting value range will be different from above range. In this case, set 0(Linear) to acceleration/
deceleration 1 pattern (f502: 0x2502). (S-pattern isn't supported.)

6.1.9. Object 0x6049: vl_velocity_deceleration

This object shall indicate the configured delta speed and delta time of the slope of the deceleration ramp. Unit
-1
is min
.
[VF-S15]
Velocity deceleration delta speed : 225 to 30,000 min
Velocity deceleration delta time : 0 to 3,600 s
[VF-AS3]
Velocity deceleration delta speed : 225 to 32,700 min
Velocity deceleration delta time : 0 to 6,000 s
Note: Do not change the acceleration/deceleration time unit (parameter f519), if change the parameter,
the setting value range will be different from above range. In this case, set 0(Linear) to acceleration/
deceleration 1 pattern (f502: 0x2502). (S-pattern isn't supported.)

6.1.10. Object 0x604A: vl_velocity_quick_stop

This object indicates the configured delta speed and delta time of the slope of the deceleration ramp for quick
-1
stop. Unit is min
.
-1
-1
-1
-1
- 32 -
E6581911
-1
). The