Huawei LUNA2000-2.0MWH-1H0 User Manual page 166

Mart string ess
Hide thumbs Also See for LUNA2000-2.0MWH-1H0:
Table of Contents

Advertisement

LUNA2000-2.0MWH-1H0, 2H0 Smart String ESS
User Manual
Alar
Alarm
m ID
Name
3043
The SOH
of the
ESM is
low.
3041
Loose
copper
bar
connectio
n for the
battery
module
3048
ESM
Auxiliary
Power
Supply
Fault
Issue 02 (2021-11-15)
Severit
Possible Causes
y
Warnin
Cause ID = 2
g
The battery module
SOH is too low.
Major
Cause ID = 1
The copper bar of the
battery module is
loosely connected.
Warnin
Cause ID = 1
g
The relay control of the
black start auxiliary
power is faulty.
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting Suggestions
1. Confirm the position of [ESR-
CabinetNo ESM-SlotNo] and the
corresponding input and output
circuit breakers of the ESC.
2. Send a shutdown command, turn off
the battery switch, bus switch, and
AC power supply switch, and wait for
5 minutes.
3. Replace the [ESR-CabinetNo ESM-
SlotNo] battery module by referring
to the quick installation guide of the
product.
4. Check that the power and monitoring
cables are securely connected. Turn
on the AC power supply switch,
battery switch, and bus switch in
sequence to deliver a startup
command.
5. If the alarm persists, contact your
dealer or technical support.
1. Confirm the position of [ESR-
CabinetNo ESM-SlotNo] and the
corresponding input and output
circuit breakers of the ESC.
2. Send a shutdown command, turn off
the battery switch, bus switch, and
AC power supply switch, and wait for
5 minutes.
3. Check whether the [ESR-CabinetNo
ESM-SlotNo] battery module copper
bar is securely connected by referring
to the quick installation guide of the
product.
4. Check that the power cables are
securely connected. Turn on the AC
power supply switch, battery switch,
and bus switch in sequence to deliver
a startup command.
5. If the alarm persists, contact your
dealer or technical support.
1. Locate the input and output circuit
breakers associated with [ESC-No].
2. Send a shutdown command, turn off
the battery switch, bus switch, and
10 Alarm Reference