4.2.4 Grounding the ESS

Prerequisites
● The grounding should comply with the local electrical safety regulations.
● Do not connect devices such as fuses and switches to ground cables.
● Connect ground cables to the ground points of the ESS enclosure or the main
Context
The ESS can be grounded using ground lugs or ground cables. The requirements
are as follows:
Connect ground cables
Method 1:Connect ground cables to the ground points of the ESS enclosure
Step 1 Connect ground cables to the ground points of the ESS using M12x30 stainless
steel bolt assemblies. The ground cables can be routed through plastic-coated
metal hoses based on site requirements.
Issue 02 (2021-11-15)
CA UTION
ground bar of the control unit cabin based on site requirements.
The ESS is installed.
The grounding requirements are clear.
Ground lug: Use ground lugs made of hot-dip zinc-coated flat steel with a
cross-sectional area of 40 mm x 4 mm, and the concrete platforms must be
300 mm above the ground.
Ground cable
Table 4-3 Ground cable description
No.
Cable
1
Ground
cable
The specifications of the ground cable are subject to this table or calculated
according to IEC 60364-5-54.
Copyright © Huawei Technologies Co., Ltd.
Type
Cross-
Sectional
Area
Single-
16–240
core
2
mm
outdoor
copper
cable and
M12
OT/DT
terminals
4 Installation
Outer
Source
Diameter
10–32 mm
Prepared
by the
customer
78