Step 2 Adjust the height with leveling washers.
Scenario 1: The Upper Part of the Lock Tongue Interferes With the Upper Surface
of the Lock Base
(1) Position of leveling washers
a. Concrete column foundation
Use leveling washers to raise ESS by 5–10 mm on the foundation columns nearest
to the door hinge (the raising height may vary according to the actual conditions).
b. Concrete platform foundation
Use leveling washers to raise ESS by 5–10 mm on the foundation under the door
hinge (the raising height may vary according to the actual conditions).
Scenario 2: The Lower Part of the Lock Tongue Interferes With the Lower Surface
of the Lock Base
Issue 02 (2021-11-15)
Jack specification: 30 t
Position requirements: a. For the concrete column foundation scenario, place
the jack at the faulty door. b. For the concrete platform foundation scenario,
place the jack at the side of the ESS.
NO TE
Wood sleepers can be used in the following circumstances.
● Insufficient jack height: Place wood sleepers underneath the jack.
● Earth ground: Use wood sleepers to extend contact area.