Service and maintenance
10.3 Replacing a module
6. Connect the reader to the power supply using the connecting cable.
Wait until the reader has started up and is ready for operation ("PWR" LED is green).
7. Wait until the new reader is automatically assigned the IP address of the replacement
device.
If necessary, assign a unique IP address and a unique device name to the reader.
8. Start the WBM.
9. Load the configuration onto the reader using the saved XML parameter file.
10.Wait until the parameters have been restored.
Result: Following the automatic restart, the reader is ready for operation.