ABB RELION 670 Series Product Manual page 42

Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Bay control REC670 2.1 IEC
Auxiliary DC voltage
Table 11. PSM - Power supply module
Quantity
Auxiliary dc voltage, EL (input)
Power consumption
Auxiliary DC power in-rush
Binary inputs and outputs
Table 12. BIM - Binary input module
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
Counter input frequency
Oscillating signal discriminator
Debounce filter
Binary input operate time
(Debounce filter set to 0 ms)
42
M12286-1 v4
Rated value
EL = (24 - 60) V
EL = (90 - 250) V
50 W typically
< 10 A during 0.1 s
M12576-1 v8.1.1
Rated value
16
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
10 pulses/s max
Blocking settable 1–40 Hz
Release settable 1–30 Hz
Settable 1–20 ms
3 ms
1MRK 511 361-BEN D
IP15843-1 v3
Nominal range
EL ±20%
EL ±20%
-
-
IP15844-1 v1
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
-
ABB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents