ABB RELION 670 Series Product Manual page 54

Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Bay control REC670 2.1 IEC
Current protection
Table 29. Instantaneous phase overcurrent protection PHPIOC
Function
Operate current
Reset ratio
Operate time at 0 to 2 x I
set
Reset time at 2 to 0 x I
set
Critical impulse time
Operate time at 0 to 10 x I
set
Reset time at 10 to 0 x I
set
Critical impulse time
Dynamic overreach
54
M12336-1 v11
Range or value
(5-2500)% of lBase
> 95% at (50–2500)% of IBase
Min. = 15 ms
Max. = 25 ms
Min. = 15 ms
Max. = 25 ms
10 ms typically at 0 to 2 x I
set
Min. = 5ms
Max. = 15ms
Min. = 25ms
Max. = 40 ms
2 ms typically at 0 to 10 x I
set
< 5% at t = 100 ms
1MRK 511 361-BEN D
Accuracy
±1.0% of I
at I ≤ I
r
r
±1.0% of I at I > I
r
-
-
-
-
-
-
-
-
ABB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rec670

Table of Contents