ABB RELION 670 Series Product Manual page 71

Hide thumbs Also See for RELION 670 Series:
Table of Contents

Advertisement

Bay control REC670 2.1 IEC
Table 53. General current and voltage protection CVGAPC , continued
Function
Independent time delay, overvoltage at 0.8 to 1.2 x U
1 - 2
Independent time delay, undervoltage at 1.2 to 0.8 x U
step 1 - 2
Overvoltage:
Start time at 0.8 to 1.2 x U
Reset time at 1.2 to 0.8 x U
Undervoltage:
Start time at 1.2 to 0.8 x U
Reset time at 1.2 to 0.8 x U
Overvoltage:
Inverse time characteristics, see table
Undervoltage:
Inverse time characteristics, see table
High and low voltage limit, voltage dependent operation,
step 1 - 2
Directional function
Relay characteristic angle
Relay operate angle
Reset ratio, overcurrent
Reset ratio, undercurrent
Reset ratio, overvoltage
Reset ratio, undervoltage
Overcurrent:
Critical impulse time
Impulse margin time
Undercurrent:
Critical impulse time
Impulse margin time
Overvoltage:
Critical impulse time
Impulse margin time
Undervoltage:
Critical impulse time
Impulse margin time
ABB
set
set
set
set
set
set
145
146
Range or value
, step
(0.00 - 6000.00) s
,
(0.00 - 6000.00) s
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
Min. = 15 ms
Max. = 30 ms
4 curve types
3 curve types
(1.0 - 200.0)% of UBase
Settable: NonDir, forward and reverse
(-180 to +180) degrees
(1 to 90) degrees
> 95%
< 105%
> 95%
< 105%
10 ms typically at 0 to 2 x I
15 ms typically
10 ms typically at 2 to 0 x I
15 ms typically
10 ms typically at 0.8 to 1.2 x U
15 ms typically
10 ms typically at 1.2 to 0.8 x U
15 ms typically
1MRK 511 361-BEN D
Accuracy
±0.2% or ±35 ms whichever is
greater
±0.2% or ±35 ms whichever is
greater
-
-
-
-
See table
145
See table
146
±1.0% of U
at U ≤ U
r
±1.0% of U at U > U
-
±2.0 degrees
±2.0 degrees
-
-
-
-
-
set
-
-
set
-
-
set
-
-
set
-
r
r
71