Bay control REC670 2.1 IEC
Maximum 72 outputs may be activated
simultaneously with influencing factors
within nominal range. After 6 ms an
additional 24 outputs may be
activated. The activation time for the
96 outputs must not exceed 200 ms. 48
outputs can be activated during 1 s.
Continued activation is possible with
respect to current consumption but
after 5 minutes the temperature rise
will adversely affect the hardware life.
Maximum two relays per
BOM/IOM/SOM should be activated
continuously due to power dissipation.
Table 17. SOM - Static Output Module (reference standard: IEC 61810-2): Static binary outputs
Function of quantity
Rated voltage
Number of outputs
Impedance open state
Test voltage across open contact, 1 min
Current carrying capacity:
Continuous
1.0 s
Making capacity at capacitive load with the
maximum capacitance of 0.2 μF :
0.2 s
1.0 s
Breaking capacity for DC with L/R ≤ 40 ms
Operating time
ABB
Static binary output trip
48-60 VDC
6
~300 kΩ
No galvanic separation
5 A
10 A
30 A
10 A
48 V/1 A
60 V/0.75 A
< 1 ms
1MRK 511 361-BEN D
The stated operate time for functions
include the operating time for the
binary inputs and outputs.
110-250 VDC
6
~810 kΩ
No galvanic separation
5 A
10 A
30 A
10 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
< 1 ms
SEMOD175395-2 v9
47