Bay control REC670 2.1 IEC
Maximum 176 binary input channels
may be activated simultaneously with
influencing factors within nominal
range.
Table 14. IOM - Binary input/output module
Quantity
Binary inputs
DC voltage, RL
Power consumption
24/30 V, 50 mA
48/60 V, 50 mA
110/125 V, 50 mA
220/250 V, 50 mA
220/250 V, 110 mA
Counter input frequency
Oscillating signal discriminator
Debounce filter
Binary input operate time
(Debounce filter set to 0 ms)
44
The stated operate time for functions
include the operating time for the
binary inputs and outputs.
Rated value
8
24/30 V
48/60 V
110/125 V
220/250 V
max. 0.05 W/input
max. 0.1 W/input
max. 0.2 W/input
max. 0.4 W/input
max. 0.5 W/input
10 pulses/s max
Blocking settable 1-40 Hz
Release settable 1-30 Hz
Settable 1-20 ms
3 ms
1MRK 511 361-BEN D
M12573-1 v8.1.1
Nominal range
-
RL ±20%
RL ±20%
RL ±20%
RL ±20%
-
-
ABB