Bay control REC670 2.1 IEC
Table 59. Autorecloser SMBRREC
Function
Number of autoreclosing shots
Autoreclosing open time:
shot 1 - t1 1Ph
shot 1 - t1 2Ph
shot 1 - t1 3PhHS
shot 1 - t1 3Ph
shot 2 - t2 3Ph
shot 3 - t3 3Ph
shot 4 - t4 3Ph
shot 5 - t5 3Ph
Extended autorecloser open time
Minimum time CB must be closed before AR becomes ready for autoreclosing cycle
Maximum operate pulse duration
Reclaim time
Circuit breaker closing pulse length
Wait for master release
Inhibit reset time
Autorecloser maximum wait time for sync
CB check time before unsuccessful
Wait time after close command before proceeding to next shot
76
M12379-1 v11
Range or value
1 - 5
(0.000-120.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.000-60.000) s
(0.00-6000.00) s
(0.00-6000.00) s
(0.000-60.000) s
1MRK 511 361-BEN D
Accuracy
-
±0.2% or ±35 ms
whichever is greater
±0.2% or ±35 ms
whichever is greater
±0.2% or ±35 ms
whichever is greater
±0.2% or ±35 ms
whichever is greater
±0.2% or ±15 ms
whichever is greater
±0.2% or ±15 ms
whichever is greater
±0.2% or ±15 ms
whichever is greater
±0.2% or ±15 ms
whichever is greater
±0.2% or ±45 ms
whichever is greater
±0.2% or ±45 ms
whichever is greater
±0.2% or ±45 ms
whichever is greater
±0.2% or ±45 ms
whichever is greater
ABB