Section 8
Current protection
Mode: The voltage and current used for the power measurement. The setting possibilities are shown in
table 19.
Table 19:
Set value Mode
A, B, C
Arone
PosSeq
AB
BC
CA
A
B
C
The function has two stages that can be set independently.
With the parameter OpMode1(2) the function can be set Enabled/Disabled.
The function gives trip if the power component in the direction defined by the setting Angle1(2) is smaller
than the set pick up power value Power1(2)
144
Complex power calculation
© 2017 - 2023 Hitachi Energy. All rights reserved
Formula used for complex power calculation
*
*
=
×
+
×
+
S
V
I
V
I
A
A
B
B
EQUATION2055-ANSI V1 EN-US
*
=
×
-
×
S
V
I
V
I
AB
A
BC
C
EQUATION2056-ANSI V1 EN-US
*
= ×
×
S
3
V
I
PosSeq
PosSeq
EQUATION2057-ANSI V1 EN-US
*
*
=
×
-
S
V
(
I
I
)
AB
A
B
EQUATION2058-ANSI V1 EN-US
*
*
=
×
-
S
V
(
I
I
)
BC
B
C
EQUATION2059-ANSI V1 EN-US
*
*
=
×
-
S
V
(
I
I
)
CA
C
A
EQUATION2060-ANSI V1 EN-US
*
= ×
×
S
3
V
I
A
A
EQUATION2061-ANSI V1 EN-US
*
= ×
×
S
3
V
I
B
B
EQUATION2062-ANSI V1 EN-US
*
= ×
×
S
3
V
I
C
C
EQUATION2063-ANSI V1 EN-US
1MRK511407-UUS Rev. N
*
×
V
I
C
C
(Equation 59)
*
(Equation 60)
(Equation 61)
(Equation 62)
(Equation 63)
(Equation 64)
(Equation 65)
(Equation 66)
(Equation 67)
Phasor measurement unit RES670
Application manual