1MRK511407-UUS Rev. N
DRA#-Input
36
37
38
39
40
19.6.3

Function and information types

Product type IEC103mainFunType value Comment:
REL 128 Compatible range
REC 242 Private range, use default
RED 192 Compatible range
RET 176 Compatible range
REB 207 Private range
REG 150 Private range
REQ 245 Private range
RER 152 Private range
RES 118 Private range
Refer to the tables in the Technical reference manual /Station communication, specifying the information
types supported by the communication protocol IEC 60870-5-103.
To support the information, corresponding functions must be included in the protection IED.
There is no representation for the following parts:
Generating events for test mode
Cause of transmission: Info no 11, Local operation
Glass or plastic fiber should be used. BFOC/2.5 is the recommended interface to use (BFOC/2.5 is the
same as ST connectors). ST connectors are used with the optical power as specified in standard.
For more information, refer to IEC standard IEC 60870-5-103.
19.7

DNP3 Communication protocol

19.7.1

Application

For more information on the application and setting guidelines for the DNP3 communication protocol
refer to the DNP3 Communication protocol manual.
Phasor measurement unit RES670
Application manual
ACC
91
92
93
94
95
© 2017 - 2023 Hitachi Energy. All rights reserved
Station communication
IEC103 meaning
Private range
Private range
Private range
Private range
Private range
GUID-EF1F0C38-9FF6-4683-8B10-AAA372D42185 v1