Section 15
Logic
The logic also issues a three-pole tripping command when phase selection within the operating
protection functions is not possible, or when external conditions request three-pole tripping. To meet the
different double, breaker-and-a-half and other multiple circuit breaker arrangements, multiple identical
SMPPTRC (94) function blocks are provided within the IED. In such installation, use one instance of
SMPPTRC function per circuit breaker.
If the OHL is connected to the substation via more than one breaker, one SMPPTRC (94) function block
should be used for each breaker. For example when single-pole tripping and autoreclosing is used on the
line, both breakers are normally set up for 1/3-pole tripping and 1/3-phase autoreclosing. Alternatively,
the breaker chosen as master can have single-pole tripping, while the slave breaker could have three-
pole tripping and autoreclosing. In the case of a permanent fault, only one of the breakers has to be
operated when the fault is energized a second time. In the event of a transient fault the slave breaker
performs a three-pole reclosing onto the non-faulted line.
The same philosophy can be used for two-pole tripping and autoreclosing.
To prevent closing of a circuit breaker after a trip, the function offers a lockout function.
15.1.3.1

Three-pole tripping

Connect the inputs from the protection functions to the input TRINP_3P. The TMGAPC function block is
used to combine up to 32 inputs into one output. Connect the output TRIP to the binary outputs on the IO
board.
This signal can also be used for other purposes internally in the IED. An example could be the starting of
breaker failure protection. The three outputs TR_A, TR_B, and TR_C will always be activated at every
trip and can be utilized on individual trip outputs if single-pole operating devices are available on the
circuit breaker even when a three-pole tripping scheme is selected.
Set the function block to Program = 3 phase and set the required length of the trip pulse to for example,
tTripMin = 150ms.
The typical connection is shown below in
Protection functions with 3 phase
trip, for example time delayed
overcurrent protection
GUID-40F59978-9468-4491-8A25-669567A9456F V1 EN-US
Figure 84:
206
TMAGAPC
Tripping logic SMPPTRC (94) is used for a simple three-pole tripping application
© 2017 - 2023 Hitachi Energy. All rights reserved
Figure
84.
SMPPTRC (94)
I3P
I3P
V3P
V3P
BLOCK
BLOCK
BLKLKOUT
BLKLKOUT
TRINALL
TRINALL
TRINP_A
TRINP_A
TRINP_B
TRINP_B
TRINP_C
TRINP_C
TRINN
TRINN
CLLKOUT
CLLKOUT
PS_A
PS_A
BFI_3P
BFI_3P
PS_B
PS_B
PS_C
PS_C
1PTRZ
1PTRZ
1PTRGF
1PTRGF
P3PTR
P3PTR
SETLKOUT
SETLKOUT
RSTLKOUT
RSTLKOUT
FLTIAMAG
FLTIAMAG
CND
CND
FLTIAANG
FLTIAANG
RSTFLTUI
RSTFLTUI
FLTIBMAG
FLTIBMAG
FLTIBANG
FLTIBANG
FLTICMAG
FLTICMAG
FLTICANG
FLTICANG
FLTINMAG
FLTINMAG
FLTINANG
FLTINANG
FLTVAMAG
FLTVAMAG
FLTVAANG
FLTVAANG
FLTVBMAG
FLTVBMAG
FLTVBANG
FLTVBANG
FLTVCMAG
FLTVCMAG
FLTVCANG
FLTVCANG
FLTVNMAG
FLTVNMAG
FLTVNANG
FLTVNANG
1MRK511407-UUS Rev. N
TRIP
TRIP
TR_A
TR_A
TR_B
TR_B
TR_C
TR_C
TRN
TRN
TR1P
TR1P
TR2P
TR2P
TR3P
TR3P
PU_A
PU_A
PU_B
PU_B
PU_C
PU_C
PU_N
PU_N
FW
FW
REV
REV
Phasor measurement unit RES670
Application manual
M14828-7 v12