Hitachi Relion 670 Series Applications Manual page 245

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK511407-UUS Rev. N
100 MVA
100 MVA
15.65kV
ANSI09000041 V1 EN-US
Figure 100:
In order to measure the active and reactive power as indicated in figure 100, it is necessary to do the
following:
1.
Set correctly all CT and VT data and phase angle reference channel PhaseAngleRef using PCM600
for analog input channels
2.
Connect, in PCM600, measurement function to the generator CT & VT inputs
3.
Set the setting parameters for relevant Measurement function as shown in the following table:
Table 33:
Setting
Operation
PowAmpFact
PowAngComp
Mode
k
Table continues on next page
Phasor measurement unit RES670
Application manual
230kV Busbar
300/5
15/0.12kV
V
V
,
AB ,
P
Q
G
4000/5
Single line diagram for generator application
General settings parameters for the Measurement function
Short description
Operation Off/On
Amplitude factor to scale power
calculations
Angle compensation for phase
shift between measured I & V
Selection of measured current
and voltage
Low pass filter coefficient for
power measurement, V and I
© 2017 - 2023 Hitachi Energy. All rights reserved
IED
BC
ANSI09000041-1-en.vsd
Selected
Comment
value
On
Function must be On
1.000
Typically no scaling is required
0.0
Typically no angle compensation is required. As well
here required direction of P & Q measurement is
towards protected object (as per IED internal default
direction)
Arone
Generator VTs are connected between phases (V-
connected)
0.00
Typically no additional filtering is required
Section 16
Monitoring
239

Advertisement

Table of Contents
loading

This manual is also suitable for:

Res670

Table of Contents