Hitachi Relion 670 Series Applications Manual page 219

Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK511407-UUS Rev. N
The general setting parameters for PHPIOC and SMPPTRC functions can be set as mentioned in
26
and
Table
GUID-0E6943FE-99EE-4356-BE83-CF1E5EDD62D3 V1 EN-US
Figure 88:
Table 26:
Setting
Operation
GlobalBaseSel
OpMode
StValMult
IP>>
IP>>Min
IP>>Max
EnaCurrMult
Table 27:
Setting
CondBlkMode
FltValRepMode
Operation
Program
TripLockout
AutoLock
Table continues on next page
Phasor measurement unit RES670
Application manual
27, respectively, and the connection diagram is shown in
Connection diagram of PHPIOC and SMPPTRC functions
General setting parameters for the PHPIOC function
General setting parameters for the SMPPTRC function
© 2017 - 2023 Hitachi Energy. All rights reserved
Description
Operation Off/On
Selection of one of the Global Base Value
groups
Select operation mode 2 out of 3/1 out of 3
Multiplier for operate current level
Operate phase current level in % of IBase
Minimum used operate phase current level in %
of IBase, if IP>> is less than IP>>Min, then IP>>
is set to IP>>Min
Maximum used operate phase current level in
% of IBase, if IP>> is greater than IP>>Max,
then IP>> is set to IP>>Max
Enable/disable current multiplier
Description
Conditional blocking mode of function due to
analog data quality
Selection of trigger for fault record 0-Do not
report, 1-Report at trip
Operation Off/On
Three ph; single or three ph; single, two or three
ph trip
Latch TRIP output when SETLKOUT input is
activated
Activate CLLKOUT output when TRIP output is
activated
Figure
88.
Default value
On
1
1
1.0
200
5
2500
1
Default value
0
1
On
1
0
0
Section 15
Logic
Table
213