19.2.2

Setting guidelines

There are two settings related to the IEC 61850–8–1 protocol:
Operation: User can set IEC 61850 communication to Enabled or Disabled.
GOOSEPortEd1: Selection of the Ethernet link where GOOSE traffic shall be sent and received. This is
only valid for Edition 1 and can be ignored if Edition 2 is used. For Edition 2, the Ethernet link selection is
done with the Ethernet Configuration Tool (ECT) in PCM600.
19.2.3

Horizontal communication via GOOSE

19.2.3.1

Sending data

In addition to the data object and data attributes of the logical nodes, it is possible to send the outputs of
the function blocks using the generic communication blocks. The outputs of this function can be set in a
dataset and be sent in a GOOSE Control Block to other subscriber IEDs. There are different function
blocks for different type of sending data.
Generic communication function for single point indication SPGAPC, SP16GAPC
Application
Generic communication function for Single Point Value (SPGAPC) function is used to send one single
logical output to other systems or equipment in the substation. SP16GAPC can be used to send up to 16
single point values from the application functions running in the same cycle time. SPGAPC has one
visible input and SPGAPC16 has 16 visible inputs that should be connected in the ACT tool.
Setting guidelines
There are no settings available for the user for SPGAPC.
Generic communication function for Measured Value MVGAPC
Application
Generic communication function for measured values (MVGAPC) function is used to send the
instantaneous value of an analog signal to other systems or equipment in the substation. It can also be
used inside the same IED, to attach a RANGE aspect to an analog value and to permit measurement
supervision on that value.
Setting guidelines
The settings available for Generic communication function for Measured Value (MVGAPC) function
allows the user to choose a deadband and a zero deadband for the monitored signal. Values within the
zero deadband are considered as zero.
The high and low limit settings provides limits for the high-high-, high, normal, low and low-low ranges of
the measured value. The actual range of the measured value is shown on the range output of MVGAPC
function block. When a Measured value expander block (RANGE_XP) is connected to the range output,
the logical outputs of the RANGE_XP are changed accordingly.
19.2.3.2

Receiving data

The GOOSE data must be received at function blocks. There are different GOOSE receiving function
blocks depending on the type of the received data. Refer to the Engineering manual for more information
about how to configure GOOSE.
Phasor measurement unit RES670
Application manual
© 2017 - 2023 Hitachi Energy. All rights reserved
Section 19
Station communication
SEMOD55317-5 v7
GUID-9888ECAD-8221-4B31-A443-EB1E3A9022C4 v1
SEMOD55999-1 v5
SEMOD55350-5 v8
SEMOD55376-5 v5
SEMOD55402-1 v3
SEMOD55872-5 v10
SEMOD55424-5 v5
GUID-CAE4B020-7131-49BF-BA29-3EEE0EFEA2B8 v2