Imin: The minimum pickup level setting should be set as % of IBase. This setting enables the function to
start detecting delta. Typical setting is 10% of IBase.
MeasMode: To detect the mode of measurement; phase to phase or phase to ground.
OpMode: To select the mode of operation. For protection applications, this should be set to
Instantaneous 1 cycle old. Load supervision can be done using DFT mag mode.
DelI>: To detect the pickup value for instantaneous sample, RMS, DFT mag based delta detection. Set a
typical value of 200% of IBase to use this function as fault detection.
DeltaT: This setting defines the number of old cycles data to be used for delta calculation in RMS/DFT
Mag mode. Typical value is 2 cycles.
tHold: This setting defines the pulse length for supervision pickup signal. Typical value is 100 ms.
EnaHarm2Blk: This setting should be set to ON, to enable blocking for heavy inrush currents or other
sources of 2
Harm2BlkLev: This is the blocking level of 2
setting is 15% of fundamental signal.
EnStValAdap: This setting should be set to ENABLE in special networks where settings in the network
are adapted with respect to 3
Harm3Level: This is the set level of 3
should be modified. Typical setting is 15% of fundamental signal.
StValGrad: To modify the DelI> based on 3
13.5

Delta supervision of real input DELSPVC

13.5.1

Identification

Function description
Delta supervision of real input
13.5.2

Application

Delta supervision of real input DELSPVC is a general processed input delta supervision. It is used to
configure any processed inputs such as:
Power (S)
Active power (P)
Reactive power (P)
Thermal heat content (ɸ)
Energy
The change over time of these quantities with respect to the old value can be supervised with this
function.
Phasor measurement unit RES670
Application manual
nd
harmonic injections.
rd
harmonic level.
rd
IEC 61850
identification
DELSPVC
© 2017 - 2023 Hitachi Energy. All rights reserved
nd
harmonic with respect to the fundamental signal. Typical
harmonic with respect to fundamental signal at which the DelI>
rd
harmonic level. Typical setting is 10% to modify the DelI>.
IEC 60617
identification
Secondary system supervision
GUID-470F7470-F3D1-46BC-B0EA-CD180FBA0AB2 v1
GUID-66CFBA71-B3A4-489F-B7F4-F1909B75E1DD v1
ANSI/IEEE C37.2
device number
GUID-C7F56ACE-D1F2-4F33-96CA-108D7F11FDD5 v1