15.10

Integer to Boolean 16 conversion IB16

15.10.1

Identification

Function description
Integer to boolean 16 conversion
15.10.2

Application

Integer to boolean 16 conversion function (IB16) is used to transform an integer into a set of 16 binary
(logical) signals. It can be used – for example, to connect integer output signals from one function to
binary (logical) inputs to another function. IB16 function does not have a logical node mapping.
The Boolean 16 to integer conversion function (IB16) will transfer a combination of up to 16 binary inputs
INx where 1≤x≤16 to an integer. Each INx represents a value according to the table below from 0 to
32768. This follows the general formula: INx = 2
activated INx will be available on the output OUT as a sum of the values of all the inputs INx that are
activated. OUT is an integer. When all INx where 1≤x≤16 are activated that is = Boolean 1 it corresponds
to that integer 65535 is available on the output OUT. IB16 function is designed for receiving up to 16
booleans input locally. If the BLOCK input is activated, it will freeze the output at the last value.
Values of each of the different OUTx from function block IB16 for 1≤x≤16.
The sum of the value on each INx corresponds to the integer presented on the output OUT on the
function block IB16.
Name of input
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
222
IEC 61850
identification
IB16
Type
Default
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
BOOLEAN
0
© 2017 - 2023 Hitachi Energy. All rights reserved
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
x-1
where 1≤x≤16. The sum of all the values on the
Description
Value when
activated
Input 1
1
Input 2
2
Input 3
4
Input 4
8
Input 5
16
Input 6
32
Input 7
64
Input 8
128
Input 9
256
Input 10
512
Input 11
1024
Input 12
2048
Input 13
4096
Input 14
8192
Input 15
16384
Input 16
32768
1MRK511407-UUS Rev. N
SEMOD158367-1 v2
SEMOD167941-2 v3
SEMOD158499-5 v5
Value when
deactivated
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Phasor measurement unit RES670
Application manual