Section 16
Monitoring
Remember that values of parameters set elsewhere are linked to the information on a report. Such
parameters are, for example, station and object identifiers, CT and VT ratios.
16.7
Logical signal status report BINSTATREP
16.7.1
Identification
Function description
Logical signal status report
16.7.2
Application
The Logical signal status report (BINSTATREP) function makes it possible to poll signals from various
other function blocks.
BINSTATREP has 16 inputs and 16 outputs. The output status follows the inputs and can be read from
the local HMI or via SPA communication.
When an input is set, the respective output is set for a user defined time. If the input signal remains set
for a longer period, the output will remain set until the input signal resets.
INPUTn
OUTPUTn
IEC09000732 V1 EN-US
Figure 103:
16.7.3
Setting guidelines
The pulse time t is the only setting for the Logical signal status report (BINSTATREP). Each output can
be set or reset individually, but the pulse time will be the same for all outputs in the entire BINSTATREP
function.
16.8
Limit counter L4UFCNT
254
There is a risk of flash wear out if the disturbance report triggers too often.
IEC 61850
identification
BINSTATREP
t
BINSTATREP logical diagram
© 2017 - 2023 Hitachi Energy. All rights reserved
GUID-E7A2DB38-DD96-4296-B3D5-EB7FBE77CE07 v2
GUID-E0247779-27A2-4E6C-A6DD-D4C31516CA5C v3
IEC 60617
ANSI/IEEE C37.2
identification
device number
-
-
t
IEC09000732-1-en.vsd
GUID-BBDA6900-4C1A-4A7C-AEA5-3C49C2749254 v2
Phasor measurement unit RES670
1MRK511407-UUS Rev. N
GUID-F9D225B1-68F7-4D15-AA89-C9211B450D19 v3
GUID-22E141DB-38B3-462C-B031-73F7466DD135 v1
Application manual