Lenovo ThinkSystem SD650 Manual page 174

Hide thumbs Also See for ThinkSystem SD650:
Table of Contents

Advertisement

Severity: Error
User Action:
Complete the following steps:
1. If this is a newly installed option, ensure that matching processors are installed in the correct
processor sockets.
2. Check Lenovo Support site for an applicable service bulletin that applies to this processor error.
3. If the problem persists, collect Service Data logs and contact Lenovo Support.
Note: The solution for this error may involve a system board replacement. If TPM encryption has
been enabled, back up TPM Encryption Recovery Key.
• FQXSFPU0007K: Processors have mismatched Internal DDR Frequency
Severity: Error
User Action:
Complete the following steps:
1. Verify that matching DIMMs are installed in the correct population sequence. Correct any
configuration issues found.
2. If the problem persists, collect Service Data logs and contact Lenovo Support.
Note: The solution for this error may involve a system board replacement. If TPM encryption has
been enabled, back up TPM Encryption Recovery Key.
• FQXSFPU0008K: A core speed mismatch has been detected for one or more processors.
Severity: Error
User Action:
Complete the following steps:
1. Verify that matching processors are installed in the correct processor sockets. Correct any mismatch
issues found.
2. Check Lenovo Support site for an applicable service bulletin or firmware update that applies to this
processor error.
3. If the problem persists, collect Service Data logs and contact Lenovo Support.
Note: The solution for this error may involve a system board replacement. If TPM encryption has
been enabled, back up TPM Encryption Recovery Key.
• FQXSFPU0009K: An external clock frequency mismatch has been detected for one or more
processors.
Severity: Error
User Action:
Complete the following steps:
1. Verify that the processor is a valid option that is listed as a Server Proven device for this system. If
not, remove the processor and install one listed on the Server Proven website.
2. Verify that matching processors are installed in the correct processor sockets. Correct any mismatch
found.
3. Check Lenovo Support site for an applicable service bulletin or firmware update that applies to this
processor error.
4. If the problem persists, collect Service Data logs and contact Lenovo Support.
170
ThinkSystem SD650 Dual Node DWC Tray and NeXtScale n1200 DWC Enclosure Messages and Codes Reference

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nextscale n12007x585468

Table of Contents