5. Make sure that power supplies fans are running with higher speed than system fan.
6. If condition presists after above inspection, reseat power supply.
7. If OT warning continues to present after power supply reseat, replace power supply.
• 99 : PS6_No_Present
Power supply was removed from chassis.
Severity
Info
Serviceable
Automatically notify support
User Action
1. No user action needed.
• A0 : Node01_BMC_Fault
The management device on indicated node is not responding.
Severity
Critical
Serviceable
Automatically notify support
User Action
Complete the following steps:
1. Reseat Node. If fault still persist, replace node.
• A1 : Node02_BMC_Fault
The management device on indicated node is not responding.
Severity
Critical
Serviceable
Automatically notify support
User Action
Complete the following steps:
1. Reseat Node. If fault still persist, replace node.
• A2 : Node03_BMC_Fault
The management device on indicated node is not responding.
Severity
Critical
Serviceable
Automatically notify support
User Action
Complete the following steps:
234
ThinkSystem SD650 Dual Node DWC Tray and NeXtScale n1200 DWC Enclosure Messages and Codes Reference