User Action
Complete the following steps:
1. Make sure that room temperature is maintained at required level.
2. Make sure that all system fan modules are installed and operating properly.
3. Make sure that all PSUs are installed and operating properly.
• BE : Leak_Snsr1_FAULT
For water cool related setup only, this event indicates that a leakage is detected in fan bay#1 drip tray.
Severity
Critical
Serviceable
Automatically notify support
User Action
Complete the following steps:
1. Check the drip tray first to see if there is water leakage.
2. Inspect and replace the water pipe,if there is water leakage.
3. Reseat the drip tray if there is no fluid in the tray,
4. Replace the drip tray if the event continue to be asserted after drip tray reseat.
• BF : Leak_Snsr2_FAULT
For water cool related setup only, this event indicates that a leakage is detected in fan bay#3 drip tray.
Severity
Critical
Serviceable
Automatically notify support
User Action
Complete the following steps:
1. Check the drip tray first to see if there is water leakage.
2. Inspect and replace the water pipe,if there is water leakage.
3. Reseat the drip tray if there is no fluid in the tray,
4. Replace the drip tray if the event continue to be asserted after drip tray reseat.
• C0 : First_Perm_Fail
Node pre-boot power permission is denied. Node is not allowed to turn on because chassis power might
be overloaded when indicated node run in fully stressed condition.
Severity
Warning
Serviceable
Automatically notify support
User Action
Complete the following steps:
.
241
Chapter 5
FPC events