Galvanic Isolation Specifications; Emc Specifications - ABB Uvisor SF910i User Manual

Integrated safeflame scanner
Table of Contents

Advertisement

A Specifications
A.3 Galvanic Isolation Specifications
A.3

Galvanic Isolation Specifications

Table A.3: Galvanic Isolation Specifications
CAN/CSA-E60730-1 and UL 60730-1
Rated impulse voltage
A.4

EMC Specifications

Follow the below standards:
IEC 61000-6-2
IEC 61000-6-4
IEC 61000-4-29
IEC 61326-3-1
IEC 60730-1/CAN/CSA E60730-1
EN 298 and EN 13611
Table A.4: EMC Specifications - 1
Category/Purpose
Electro Static Discharge (ESD) Immunity
Radiated, Radio-Frequency, and
Electromagnetic Field Immunity
Electrical Fast Transient (Burst) Immunity
Surge Immunity
8VZZ005286 B
500V
between enclosure earth and all terminal blocks (except relay
AC
contacts and +24V
terminal).
DC
1500V
between enclosure earth and relay contacts and between relay
AC
contacts
Standards
IEC 61000-4-2
IEC 61326-3-1
EN 13611
IEC 61000-4-3
IEC 61326-3-1
EN 13611
IEC 61000-4-4
IEC 61326-3-1
EN 13611
IEC 61000-4-5
IEC 61326-3-1
Test Severity levels
Design Level/Acceptance Criteria
± 8 KV contact discharge
± 15 KV air discharge
80 - 1000MHz 20V/m
1400 - 6000MHz 10V/m
80% Amplitude Modulated
(1 KHz, sin.)
Relay contacts:
3 kV (5/50ns, 5 kHz)
Others and Earth:
2 kV (5/50ns, 5 kHz)
Relay contacts:
2 kV (line to line)