A Specifications
A.4 EMC Specifications
Table A.4: EMC Specifications - 1
(Continued)
Category/Purpose
Conducted Disturbances Immunity,
induced by radio-frequency fields
Magnetic Field Immunity
Table A.5: EMC Specifications - 2
Category/Purpose
Conducted, Common Mode Disturbances
Immunity
Voltage Dips and Interruptions Immunity
Radiated Emission and Conducted
Emissions
8VZZ005286 B
Standards
EN 13611
IEC 61000-4-6
IEC 61326-3-1
EN 13611
IEC 61000-4-8
EN 13611
Standards
IEC 61000-4-16
IEC 61326-3-1
IEC 61000-4-29
IEC 61326-3-1
EN13611
IEC 61000-6-4
Design Level/Acceptance Criteria
4 kV (line to ground)
Others:
2 kV (line to ground)
10 V (150 kHz to 80 MHz, 1 kHz (80 %
AM))
30 A/m cont., 300 A/m for 1s
Design Level/Acceptance Criteria
Severity Level 3
1 V to 10 V, 20 dB/Decade (1,5 kHz to 15
kHz)
10 V (15 kHz to 150 kHz)
10 V (DC, 16 2/3 Hz, 50/60 Hz and
150/180 Hz)
100 V short duration (1s, DC, 16 2/3 Hz
and 50/60 Hz)
Voltage dips: 40% and 70% UT for 10ms
Short interruption: 0% UT for 10ms and
20ms
0V and Recorded Voltage to 10%
CISPR 11:2015/AMD1:2016
CISPR 16-1-1:2015
Group1, Class A, ISM Equipment