3 Installation
3.3 Product Installation
Supply generally includes all the indicated accessories, specially designed to easy the
assembly/dismantling and the aiming of the Flame Scanner.
To provide a LOS (also called direct view) installation, drill a 55 mm hole in the burner
plate according to the drilling template and fit the swivel flange basement (see
E.2).
In case, a single scanner shall detect both the igniter and main flame, aim the scanner
to the primary zone of the main burner flame in a point where the pilot flame intersect
the main flame. The effect of any turbulence set by the air register must also be taken
into consideration to ensure that the pilot flame involves the targeted zone of the scanner.
Connect the air flexible hose in the ¾" provision on the "Y" union (see
SF910i - FOC (Fiber Optic Cable Installation)
The typical application of fiber optic extensions are:
Flexible-extended for corner fired tilting burners
Rigid-extended for fixed burners large wind box
The extended Flame Scanner includes both internal and external carrier. The external
extension pipe (outer carrier) may be considered a semi-permanent component of the
burner or relevant air box. Once mounted, it needs no care or maintenance.
Only the inner carrier, housed in the outer one, incorporates components that may need
maintenance and/or replacement (optic fiber lens).
Basic premises to determine the final location of the extended Flame Scanner are:
Define where to weld the collar in the burner bucket.
Make sure levers or other mechanical parts do not crunch, bang, or cut the outer
carrier inside the burner vane.
Test the corner tilt within the full range and make sure that the flexible extension
doesn't bend sharply.
The end part of the outer carrier must be let free to slide inside the collar. The flexible
part of the extended scanner shall work as a spring keep pressing the end part into
the collar.
The extended Flame Scanner requires, in all versions, low-pressure air (preferably
supplied by booster fan). This air is used for cooling and cleaning purposes. See
specification for air requirement.
8VZZ005286 B