F Cables
F.2 Cabling
F.2

Cabling

SF910i can be wired to external devices using standard cables available on the market.
The following tables specifies the technical requirement for the SF910i cables except
SF910i-L.
Note that in this case, ABB does not specify mechanical properties, global cross sections,
fire resistance properties, and so on. The following are the minimum electrical
requirements.
Table F.1: 24 V
Conductor(s) section
Conductor(s) material
Colors
Shield
Conductor resistance
Isolation resistance
Working voltage
Table F.2: Relays Contacts
Conductor(s) section
Conductor(s) material
Colors
Shield
Conductor resistance
Isolation resistance
Working voltage
8VZZ005286 B
Power Supply
DC
Type
Type
Pair
2
1 mm
each
Copper
Conductor 1: red
Conductor 2: black
Not required
<= 20 Ohm/Km (at 20ºC)
>= 1000 MOhm x Km (at 20ºC)
< 50V
DC
Three Conductors
2
0.5mm
each
Copper
Conductor 1: Orange
Conductor 2: Light-blue
Conductor 3: Pink
Not required
<= 20 Ohm/Km (at 20ºC)
>= 1000 MOhm x Km (at 20ºC)
Up to 50V
AC