8 Configuration-Mode

8.3 Configuration Menu Descriptions

8.2.2

Exiting Configuration-Mode

Exit the Configuration-Mode by holding in the d pushbutton for two seconds. If there is
no user activity for 20 seconds, the SF910i will automatically transfer to the Normal-Mode.
8.3
Configuration Menu Descriptions
The specific Configuration-Mode functions are described in the following sections in the
order of appearance on the Configuration-Mode menu.
8.3.1

Operating-Mode

Operating-Mode can be:
Corner
Wall/Industrial
Lighter
Turbine
8.3.2

Application Select

Use High Limit
This function activates the High-Limit trip function for this channel. If the High-Limit
function is activated, the SF910i will vote a Flame-Off condition when the
Measured-Values exceed the programmed High-Limit values.
In most applications, the High-Limit function is OFF.
Use AC-Amplitude
This function activates the AC-Amplitude trip point for this channel. If AC-Amplitude is
activated, the SF910i will vote a Flame-Off condition, if the ACAmplitude drops below
the programmed Drop-Out value.
In most applications, the AC-Amplitude function is OFF.
8.3.3

Change IDS

Each unit can be uniquely identified using three category fields. Each field can have up
to four alphanumeric characters. These IDs are NOT required for basic flame detection.