Tubing Data And Refrigerant; Tubing Data For Dhw And Outdoor Unit Combination; Paw-Vp1000Ldhw - Panasonic PRO-HT Tank Series Technical Manual

Table of Contents

Advertisement

5

Tubing Data and Refrigerant

5.1

Tubing data for DHW and outdoor unit combination

5.1.1 PAW-VP1000LDHW

Indoor Unit
PAW-VP1000LDHW
Tubing data
Tubing size outer diameter Refrigerant
connection pipe
Indoor unit pipe junction
Outdoor unit pipe junction
Wall thickness of the insulation
Limit of tubing length (L)
Height differential of Indoor/ Outdoor
units (H1)
Attention: follow instruction
Required additional refrigerant over 7,5 meters
Refrigerant charged at shipment R410A
Indoor Unit
PAW-VP1000LDHW
Tubing data
Tubing size outer diameter
Refrigerant connection pipe between SVK
and Tank
Indoor unit pipe junction
Wall thickness of the insulation
Limit of tubing length (L)
Height differential of Indoor/
Outdoor units (H1)
Attention: follow instruction
Indoor Outdoor ratio
Refrigerant charged at shipment R410A
*The system must have extra refrigerant filling, please see installation manual for U-16MF3E8.
Between SVK Box and Tank other charge calculation must be done according to MF3 installation manual.
Pipe connection between distribution joint and SVK box refer to installation manual.
PAW-VP•LDHW - Technical Manual – 2020-07
Liquid tube
[mm (inch.)]
Gas tube
[mm (inch.)]
Liquid tube
[mm (inch.)]
Gas tube
[mm (inch.)]
Liquid tube
[mm (inch.)]
Gas tube
[mm (inch.)]
Liquid tube
Gas tube
Outdoor unit is placed higher
Outdoor unit is placed lower
Liquid tube
[mm (inch.)]
Gas tube
[mm (inch.)]
Liquid tube
[mm (inch.)]
Gas tube
[mm (inch.)]
Liquid tube
Gas tube [mm]
Outdoor unit is placed higher
Outdoor unit is placed lower
Indoor unit capacity not more than [%] of
Outdoor capacity
Tubing Data and Refrigerant
Outdoor Unit
U-250PE2E8A
Ø 9.52 (3/8)
Ø 19.05 (3/4)
Ø brazing 12.7 (1/2)
Ø brazing 19.05 (3/4)
Ø flared connection 12.7 (1/2)
Ø flared connection 25.4 (1)
[mm]
>10
[mm]
>19
[m]
30
[m]
30
[m]
30
Remove 1400 g for pipe length 7.5 m
[g/m]
45 (>7.5m = -1400 g + 45 g/m)
[kg]
6.4
Outdoor Unit
U-16MF3E8
Ø 9.52 (3/8)
Ø19.08 (3/4)
Ø brazing 12.7 (1/2)
Ø brazing 19.05 (3/4)
[mm]
>10
>19
[m]
50
[m]
30
[m]
30
*
130
[kg]
8.3
5
51