Dn" Code Setting List - Panasonic PRO-HT Tank Series Technical Manual

Table of Contents

Advertisement

How to make Settings

9.1.6 "DN" code setting list

!
i
9
80
Important
All settings are necessary, otherwise faultless operation is not possible. Please follow the se-
quence described above!
M PAW-VP1000LDHW; PAW-VP750LDHW – U-16MF3E8 (VRF)
Indoor Unit Tank detailed settings; Remote controller CZ-RTC5B
Parameter
Default
"DN" code
value
10
0006
11
0015
06
0000
0b
0002
0C
0000
0d
0000
15
0022
16
0000
21
0030
22
0018
28
0001
2C
0000
2d
0008
Note
"DN" codes 10 & 11 must be set first.
Outdoor unit detailed settings by CZ-RTC2/4
Parameter
Default
"DN" code
value
15
000
35
000
36
000
4b
001
50
000
7b
001
8d
045
* to be purchased separately
New value
Explanation
to set
0031
Unit Type
0023
Capacity code
Inlet temperature shift in heating mode.
0000
non-active
0001
EXCT setting
0001
Heating preparation display
0001
Cool/ Heat auto non-active
0013
0000
Fan speed not displayed
0055
Heating upper limit 55°C
0035
Heating lower limit 35°C
0001
Automatic restart after power failure activated
0000
Expansion valve setting
0008
Operation mode DHW
New value
Explanation
to set
005
Specific Tank setting
-05
Specific Tank setting
-05
Specific Tank setting
003
Tank setting
001
Evaporation temperature shift by indoor unit type
003
Air to Water indoor unit connection permission
055
Set temperature upper limit
Check and adjust
Check and adjust
PAW-VP•LDHW - Technical Manual – 2020-07