Selection and protection of a motor
Pr. 71 (Pr. 450) Setting
Pr. 71
Pr. 450
4
Standard motor
Constant-torque motor
Vector control dedicated motor
14
SF-V5RU (except for 1500 r/min
series).
Mitsubishi standard motor
(SF-JR 4P 1.5kW or less)
24
thermal characteristic for the
constant-torque motor
Vector control dedicated motor
34
SF-V5RU (1500r/min series),
SF-THY
Mitsubishi High efficiency motor
44
(SF-HR)
Mitsubishi constant-torque
54
motor (SF-HRCA)
Standard motor
5
15
Constant-torque motor
6
Standard motor
Constant-torque motor
16
7
Standard motor
17
Constant-torque motor
Standard motor
8
Constant-torque motor
18
9999
(initial
Without second applied motor
value)
*1
Motor constants of Mitsubishi high efficiency motor SF-HR.
*2
Motor constants of Mitsubishi constant-torque motor SF-HRCA.
*3
Select this setting for vector control dedicated motor SF-V5RU (except for 1500 r/min series).
REMARKS
 When performing offline auto tuning, set "3, 7, 8, 13, 17, 18, 23, 33, 43, 53" in Pr. 71.
(Refer to page 192 for offline auto tuning)
 For the FR-A720-00240, 00330 and FR-A740-00120, 00170, the Pr. 0 Torque boost and Pr. 12 DC injection brake operation voltage
settings are automatically changed according to the Pr. 71 setting as follows.
Standard Motor Setting
Pr. 71
0, 2, 3 to 8, 20, 23, 24, 40, 43, 44
Pr. 0
Pr. 12
190
Thermal Characteristic of the Electronic Thermal Relay
Function
Constant Torque Motor Setting
1, 13 to 18, 50, 53, 54
3%
4%
Auto tuning data can be
read, changed, and set
Star
Direct input of
connection
motor
constants is
Delta
enabled
connection
Motor
Star
constants
connection
direct input
+
Delta
offline auto
connection
tuning
2%
2%
Motor ( : used motor)
Constant
Standard
torque
(SF-JR etc.)
(SF-JRCA etc.)
*1

*2
Vector
(SF-V5RU)

*3