Frequency/torque setting by analog
input (terminal 1, 2, 4)
(5) Frequency setting voltage (current) bias/gain adjustment method
(a)Method to adjust any point by application of voltage (current) to across the terminals 2 and 5 (4 and 5).
Operation
1.
Confirm the RUN indicator and operation mode
indicator
The inverter must be at a stop.
The inverter must be in the PU operation mode.
(Using
)
2.
Press
to choose the parameter setting mode.
3.
Turn
until
4.
Press
to display
5.
Turn
until
appears. Set to C4 Terminal 2 frequency
setting gain.
6.
Press
to display the analog voltage (current)
value (%).
7.
Apply a 5V (20mA) voltage (current).
(Turn the external potentiometer connected
across terminals 2 and 5 (across terminals 4
and 5) to maximum (any position).)
CAUTION
After performing the operation in step 6, do not touch
completion of calibration.
8.
Press
to set.
REMARKS
 If the frequency meter (indicator) connected to across terminals FM and SD does not indicate exactly 60Hz, set calibration
parameter C0 FM terminal calibration. (Refer to page 267)
 If the gain and bias frequency settings are too close, an error (
302
appears.
.
(
)
By turning
, you can read another parameter.
Press
to return to the
Press
twice to show the next parameter (
Display
Terminal 2 input Terminal 4 input
* The value is nearly 100 (%) in the maximum
position of the potentiometer.
until
*
Flicker...Parameter setting complete!!
(Adjustment completed)
* The value is nearly 100 (%) in the maximum
position of the potentiometer.
indication (step 4).
) may be displayed at the time of write.
The parameter
number read
previously appears.
C0 to C41
setting
is enabled.
Analog voltage (current)
value (%) across terminals 2 and 5
(across terminals 4 and 5)
*
Terminal 2 input Terminal 4 input
).