c) Method to adjust torque only without adjustment of gain voltage (current)
(when changing gain torque from 150% to 130%)
Operation
1.
(Pr.933) appears.
2.
Press
to show the present set value.
(150%)
3.
Turn
o change the set value to
"
" (130.0%)
4.
Press
to set.
5.
Mode/monitor check
Press
twice to choose the
monitor/frequency monitor.
6.
Apply a voltage across the inverter
terminals 1 and 5 (across 4 and 5) and
turn on the start command (STF, STR).
Operation starts with 130% torque.
REMARKS
· For operation from the parameter unit (FR-PU04/FR-PU07), refer to the instruction manual of the FR-PU04/FR-PU07.
· Set bias torque setting using calibration parameter C16 (Pr. 919) or C38 (Pr. 932). (Refer to page 306 )
Be cautious when setting any value other than "0" as the bias torque at 0V (0mA). Torque is applied to the motor
by merely tuning ON the start signal without torque command.
Parameters referred to 
Pr. 20 Acceleration/deceleration reference frequency
Pr. 73 Analog input selection, Pr. 267 Terminal 4 input selection
Pr. 79 Operation mode selection
Pr. 858 Terminal 4 function assignment, Pr. 868 Terminal 1 function assignment
Pr.920) or
Flicker...Parameter setting complete!!
CAUTION
Refer to page 175
Refer to page 291
Refer to page 321
Frequency/torque setting by analog
input (terminal 1, 2, 4)
Display
or
Terminal 1 input
Terminal 4 input
Terminal 1 input Terminal 4 input
Refer to page 290
4
309