Connection of stand-alone option units
FR-A720-00460, FR-A740-00230 and 00310
Connect the brake resistor
across terminals P/+ and PR.
Brake resistor
* Do not remove the jumper across terminal P/+ and P1 except when connecting a DC reactor.
When the regenerative brake transistor is damaged, the following sequence is recommended to prevent overheat
and burnout of the brake resistor.
<Example 1>
MC
Power
Supply
T
F
MC
OFF
ON
OCR
Contact
MC
FR-A720-00460 (FR-A740-00230) or more
*1
Since the
*2
Refer to the table below for the type number of each capacity of thermal relay and the diagram below for the connection. (Always install a thermal
FR-A720-00460 (FR-A740-00230) or more
relay when using the
Power Supply
High-Duty Brake
Voltage
Resistor
FR-ABR-0.4K
FR-ABR-0.75K
FR-ABR-2.2K
FR-ABR-3.7K
200V
FR-ABR-5.5K
FR-ABR-7.5K
FR-ABR-11K
FR-ABR-15K
FR-ABR-22K
FR-ABR-H0.4K
FR-ABR-H0.75K
FR-ABR-H1.5K
FR-ABR-H2.2K
FR-ABR-H3.7K
400V
FR-ABR-H5.5K
FR-ABR-H7.5K
FR-ABR-H11K
FR-ABR-H15K
FR-ABR-H22K
CAUTION
The brake resistor connected should only be the dedicated brake resistor.
The jumper across terminals PR and PX (FR-A720-00330 (FR-A740-00170) or less) must be disconnected before connecting
the dedicated brake resistor. Doing so may damage the inverter.
Brake resistor cannot be used with the brake unit, high power factor converter, power supply regeneration converter, etc.
42
Jumper *
Terminal P/+
Terminal PR
Thermal
High-duty
relay
brake resistor
(OCR)(*2)
(FR-ABR)
Inverter
R/L1
P/+
S/L2
PX
T/L3
PR
Disconnect jumper. (*1)
Thermal Relay Type
(Mitsubishi product)
TH-N20CXHZ-0.7A
TH-N20CXHZ-1.3A
TH-N20CXHZ-2.1A
TH-N20CXHZ-3.6A
TH-N20CXHZ-5A
TH-N20CXHZ-6.6A
TH-N20CXHZ-11A
TH-N20CXHZ-11A
TH-N60-22A
TH-N20CXHZ-0.24A
TH-N20CXHZ-0.35A
TH-N20CXHZ-0.9A
TH-N20CXHZ-1.3A
TH-N20CXHZ-2.1A
TH-N20CXHZ-2.5A
TH-N20CXHZ-3.6A
TH-N20CXHZ-6.6A
TH-N20CXHZ-6.6A
TH-N20-9A
FR-A720-00610 to 00900, FR-A740-00380 and 00440
Connect the brake resistor
across terminals P/+ and PR.
Jumper
Brake resistor
<Example 2>
R
Power
Supply
T
F
MC
OFF
ON
MC
inverter is not provided with the PX terminal, a jumper is not need to be removed.
)
Contact Rating
110V 5AAC,
220V 2AAC(AC-11 class)
110V 0.5ADC,
220V 0.25ADC(DC-11 class)
Terminal P/+
*
Thermal
relay
Inverter
MC
(OCR)(*2)
R/L1
P/+
S/L2
PX
T/L3
PR
Disconnect jumper. (*1)
B
C
OCR
Contact
1/L
1
2/T
1
To the inverter
P/+ terminal
Terminal PR
High-duty
brake resistor
(FR-ABR)
R
5/L
3
TH-N20
6/T
3
To the ABR