Summary of Contents for ABB D1M 15

  • Page 1 MULTIMETER D1M 15 User manual...
  • Page 3: Table Of Contents

    D1M 15 MULTIMETER USER MANUAL Table of Contents 1. General information..................... 5 1.1.Use and storage of manuals ..................5 1.2.Copyright ........................5 1.3.Liability disclaimer ....................5 1.4.General safety warnings ..................5 1.5.Cyber Security Disclaimer ..................6 2. Packaging contents ..................... 7 3. Technical characteristics ..................8 3.1.Description of the device ..................8...
  • Page 4 D1M 15 MULTIMETER USER MANUAL 8. Data reading (RED) ....................39 8.1.Realtime (REAL) ....................40 8.2.Energy (ENRG) .......................41 8.3.Power Quality (PWQT)..................42 8.4.I/O .......................... 43 8.5.Notifications (NTF)....................44 8.6.Power Outage (PWF) ....................47 9. Conclusion ......................48...
  • Page 5: General Information

    1.2.Copyright The copyright of this manual is the property of ABB LV Installation Materials Co. Ltd. Beijing. This manual contains texts, designs and illustrations of a technical nature which must not be disclosed or transmitted to third parties, even partially, without the written authorization of ABB LV Installation Materials Co.
  • Page 6: Cyber Security Disclaimer

    D1M 15 MULTIMETER USER MANUAL 1.5.Cyber Security Disclaimer D1M 15 multimeter is designed to be connected and to communicate information and data via a network interface, which should be connected to a secure network. It is your sole responsibility to provide and...
  • Page 7: Packaging Contents

    D1M 15 MULTIMETER USER MANUAL 2. Packaging contents Packaging contents Multimeter D1M 15 Installation manual Calibration certificate...
  • Page 8: Technical Characteristics

    D1M series can help users accurately monitor energy efficiency while meeting their cost control requirement. Conforming to the international electric energy metering and monitoring accuracy standards, all D1M series products are perfectly suitable for ABB electrical systems and solutions. 3.2.Main functionalities Real-time Measurement TRMS Current •...
  • Page 9: Technical Data

    D1M 15 MULTIMETER USER MANUAL 3.5.Technical data Auxiliary power supply Voltage range 100-230 V AC/DC ±15% Frequency 50 - 60Hz ±5% Power Consumption 5VA max Installation category CAT III 300V class per IEC 61010-1 edition 3 Protection fuse T1 A-277 VAC...
  • Page 10 D1M 15 MULTIMETER USER MANUAL Climatic conditions Operating temperature -5 to 55°C (K55 IEC61557-12) Storage temperature -25 to70°C (K55 IEC61557-12) ≤75% yearly average, Relative humidity ≤95% on 30 days/year Altitude ≤2km Pollution degree It is prohibited to use in the environment containing...
  • Page 11: Installation

    D1M 15 MULTIMETER USER MANUAL 4. Installation 4.1.Assembly 4.2.Disassembly...
  • Page 12: Wiring Diagrams

    D1M 15 D1M 15 Mobdus Type of network D1M 15 can be used on different type of network (please refer to chapter “7. Configuration (CFG)” for the configuration on the device). According to the type of network that has been chosen, the parameters visualized on the device HMI change.
  • Page 13 D1M 15 MULTIMETER USER MANUAL • 3-phase 3-wire network with 3CTs (3 3T) 3P3W3CT 3P3W3CT Voltage Voltage L1 L2 L3 N L1 L2 L3 N L1(A) L1(A) L2(B) L2(B) L3(C) L3(C) • 3-phase 3-wire network with 2CTs (3 2T) 3P3W2CT...
  • Page 14: Access To Device

    This chapter gives a detailed introduction of the device’s HMI, including how to read data and configure related parameters. 5.1.Display Front panel. D1M 15 products use LED displayer, the front panel of D1M 15 is shown below: Operator panel Display area Function buttons...
  • Page 15 D1M 15 MULTIMETER USER MANUAL Area Description Title of the content displayed on each screen, including MENU, Title Read and CONF… Load type Inductive load and capacitive load, or the negative sign Measurements Specific measured value, or other contents Magnitude...
  • Page 16: Buttons

    D1M 15 MULTIMETER USER MANUAL 5.2.Buttons Each D1M 15 is provided with 3 push buttons as per below picture: Functions of each button might change according to the displayed page on the meter. See below for a complete description: Button...
  • Page 17 D1M 15 MULTIMETER USER MANUAL The following will be combined with the display to describe how to complete the data entry. 1. Press “Up” to increase the numerical characters from 0 to 9, until the required character is obtained. • How to Go back to a previous number If during the data entry the desired number is exceeded by mistake, it is needed to increase the displayed number until data entry starts again from 0.
  • Page 18 D1M 15 MULTIMETER USER MANUAL Some device configurations allow entering the comma. Comma can be displayed by increasing the number with “Up” , after character 9 and before data entry starts again from character 0. • Confirm number 3. Repeat the operations described in steps 1 and 2 until the desired number is obtained, press “OK” to...
  • Page 19 D1M 15 MULTIMETER USER MANUAL • How to Enter the magnitude Some device configurations allow entering the magnitude (k, M). Once the number has been entered as after step 3, keys “Up” and “Down” allow enabling the magnitude “K” (kilo) or not. Press “OK” to confirm...
  • Page 20: First Commissioning

    D1M 15 MULTIMETER USER MANUAL 6. First commissioning When the device is started up for the first time, the basic parameters need to be set, and the wizard program will guide the user to configure the device by following the steps below:...
  • Page 21: Wiring (Wir)

    D1M 15 MULTIMETER USER MANUAL 6.2.Wiring (WIR) In order to configure the type of network it is needed to choose one of the available options according to the installation conditions. CFG>ISTL>WIR 1. Scroll the list of fields “Up” or “Down”...
  • Page 22: Vt Ratio (Vt P, Vt S)

    D1M 15 MULTIMETER USER MANUAL 6.4.VT ratio (Vt P, Vt S) D1M is capable to measure voltage via direct connection up to 300 V (L-N), or via indirect connection by means of voltage transformers. In order to configure the voltage transformer ratio, it is needed to enter manually the values of both primary (Vt P) and secondary (Vt S).
  • Page 23: Configuration (Cfg)

    D1M 15 MULTIMETER USER MANUAL 7. Configuration (CFG) When entering the CFG section, in order to change any configuration of the device, it is mandatory to enter the password. It is needed to enter the password again when customer needs to re-operate after inactivity time.
  • Page 24 D1M 15 MULTIMETER USER MANUAL Reset (RST) If the user selects “YES” and presses Button “OK”, all parameters will be reset, i.e. restoring all parameters to their factory default. CFG>UNT>RST RST sub-menu includes the following pages: Menu Description RESET FACTORY...
  • Page 25 D1M 15 MULTIMETER USER MANUAL • RESET NOTF All notification will be cleared after the reset notification, including alarms, warnings, and errors. CFG>UNT>RST>NTF • RESET Global Complete reset of the device except for the settings and the audit log, include notifications, energy.
  • Page 26 D1M 15 MULTIMETER USER MANUAL Device information (INF) INF includes firmware version, product model and peripheral functions, etc. CFG>UNT>INF Menu Description Firmware version A method for Error-Detection and Correction Serial Number D1M Device Type Energy Saving (ENS) In this menu it is possible to define the inactivity time in order to limit the device power consumption in no operation conditions.
  • Page 27 D1M 15 MULTIMETER USER MANUAL Audit log (LOG) LOG items that are counted contain the activities as below. User could read the times through HMI and communication. Description CT Primary setting CT Secondary setting VT Primary setting VT Secondary setting...
  • Page 28 D1M 15 MULTIMETER USER MANUAL Homepage Homepage can be set as the one of Summary, Phase Voltage, Line Voltage and Current page. It will turn to the home page which was set by users if no activities after inactivity time.
  • Page 29 D1M 15 MULTIMETER USER MANUAL CFG>UNT>HOMEPAGE LED is used to indicate the speed of energy consumption. It can be configured to output Total Active Import Energy(IPEN), Total Active Export Energy(EPEN), Total Reactive Import Energy(IQEN), Total Reactive Export Energy(EQEN), Total Apparent Import Energy(ISEN) and Total Apparent Export Energy(ESEN).
  • Page 30: Installation (Istl)

    (Ct P, Ct S)” “6.4.VT ratio (Vt P, Vt S)”. 7.3.Input/output (I/O) In this section it is possible to configure I/O slots of the meter. D1M 15 series Multimeter meter have two ports of DO. I/O includes the following sub-menus: Menu...
  • Page 31 D1M 15 MULTIMETER USER MANUAL Pulse settings (PUL) Selecting Pulse output, the output is set as a pulse generator associated with a measured parameter. It is needed to consecutively set a measured parameter associated to the pulse output, the pulse ratio, and the pulse length.
  • Page 32: Alarms (Alm)

    When the device is in alarm state, ICON will be displayed. Each D1M 15 provides up to 15 alarms; following parameters are available: Menu Description...
  • Page 33 D1M 15 MULTIMETER USER MANUAL CFG>ALM • “Add” indicates that the alarm is not yet present. If it needs to be added, press the button “OK” to go to the event and configure the subsequent parameters. • “Edit” indicates that the alarm is already present. If it needs to be modified, press the button “OK”...
  • Page 34 D1M 15 MULTIMETER USER MANUAL PHASE When a variable is selected, a specific phase of the variable needs to be selected. CFG>ALM>PHS Phase Description Phase 1 Phase 2 Phase 3 Total phase (when PT/QT/ST/PFT is selected variable) Different variables contain different phases, so the phase selection depends on the variable selected.
  • Page 35 D1M 15 MULTIMETER USER MANUAL CFG>ALM>STP After the number is set, it is needed to use Button “Up” and Button “Down” to adjust the magnitude. HYSTERESIS HYSTERESIS is a percentage value, and its setting range is 0%-50%. CFG>ALM>HYS DELAY DELAY is used to verify whether the variable value really exceeds the limit or is recovered, and its setting range is 1-900s.
  • Page 36 D1M 15 MULTIMETER USER MANUAL PORT Each alarm event can be connected with certain DO, and different alarms can be connected to the same CFG>ALM>POT • The optional Dos include DO1, DO2 and NONE. Only the DOs configured as alarm output can appear in the list. For details, see “7.3.Input/output...
  • Page 37: Communication (Com)

    D1M 15 MULTIMETER USER MANUAL 7.5.Communication (COM) Com menu allows to set all the parameters related to the communication protocol available for a specific product version. The embedded communication protocol varies according to the different product versions. Please refer to “3.3.Versions”...
  • Page 38 D1M 15 MULTIMETER USER MANUAL • Byte format (PAR) BYTE comprises three parts – bits per byte, parity bit and stop bit. CFG>COM>PAR The optional byte formats include: BYTE Description 8 even parity bits and 1 stop bit 8 odd parity bits and 1 stop bit 8 No Parity bits and 1 stop bit •...
  • Page 39: Data Reading (Red)

    D1M 15 MULTIMETER USER MANUAL 8. Data reading (RED) RED section allows to visualize all the parameters measured by D1M. Specifically, it includes the following menus: Menu Description REAL Real-time measurements ENRG Energy measurements PWQT Power quality State of digital input/output port...
  • Page 40: Realtime (Real)

    D1M 15 MULTIMETER USER MANUAL 8.1.Realtime (REAL) REAL means the real-time data of the current electric energy, including the following items: RED>REAL REAL Description Summary measurements, average of 3 phases VLL, average of 3 phases I, and active power total...
  • Page 41: Energy (Enrg)

    D1M 15 MULTIMETER USER MANUAL 8.2.Energy (ENRG) RED>ENRG ENRG Description PEN IMP Total imported active energy PEN EXP Total exported active energy QEN IMP Total imported reactive energy QEN EXP Total exported reactive energy SEN IMP Total imported apparent energy...
  • Page 42: Power Quality (Pwqt)

    D1M 15 MULTIMETER USER MANUAL 8.3.Power Quality (PWQT) RED>PWQT PWQT Description Per phase power factor; when WIRI is selected as ‘3 3T’, ‘3 2T’, ‘3 1T’ or ‘1N1T’, this data is absent Total power factor...
  • Page 43: I/O

    D1M 15 MULTIMETER USER MANUAL 8.4.I/O I/O sub-menu includes the reading of status and/or pulses for DO, according to the product version: Menu Description DO STA State of digital output port DO1 PUL DO1 Pulse counter DO2 PUL DO2 Pulse counter RED>I/0...
  • Page 44: Notifications (Ntf)

    D1M 15 MULTIMETER USER MANUAL 8.5.Notifications (NTF) NTF includes the following items: Menu Description Alarm list, Related to the alarm status and information Warnings list, related to installation conditions and device settings Errors list, related to the device and to its self-diagnostics Alarms (ALM) ALM is generated based on the Alarm configured by the user.
  • Page 45 D1M 15 MULTIMETER USER MANUAL Warnings (WRN) WRN is generated when the device detects the operating conditions. When there is a WARN notification, Icon will be displayed; and when there is no warn messages, Icon will disappear. WRN comprises warn count and specific warn message.
  • Page 46 D1M 15 MULTIMETER USER MANUAL Errors (ERR) ERR is generated when the device detects operating fatal conditions. When there is an ERROR notification, Icon will be displayed and it will not disappear until the error is solved. ERROR comprises error count and specific error message.
  • Page 47: Power Outage (Pwf)

    D1M 15 MULTIMETER USER MANUAL 8.6.Power Outage (PWF) PWF is used to record the number and time of power outage. The maximum record number is 999. RED>NTF>PWF In additional, record the power off as a warning in warning list, light up the warning icon after next power...
  • Page 48: Conclusion

    D1M 15 MULTIMETER USER MANUAL 9. Conclusion Thank you for using ABB D1M 15 series Multimeter and reviewing this user manual. In the future, if you encounter any problems, please contact ABB technical support, we will be happy to help you.
  • Page 49 ......................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................................