Pulse settings (PUL)
Selecting Pulse output, the output is set as a pulse generator associated with a measured parameter. It
is needed to consecutively set a measured parameter associated to the pulse output, the pulse ratio, and
the pulse length.
Electricity Variable
Description
IPEN
Import active energy
EPEN
Export active energy
IQEN
Import Reactive energy
EQEN
Export Reactive energy
ISEN
Import Apparent energy
ESEN
Export Apparent energy
NONE
Nothing
• The pulse ratio could be set manually or selected from default values. The formula guiding this
parameter setting is:
Outing pulse = X * Energy (Wh/arh/VAh)
X is the set value of pulse ratio
Default values: 10/100/1000/5000 pulses for each kWh/kvarh/kVAh or 10/50/100 pulses for each Wh/
varh/VAh.
Manual setting: 1 and 999999 pulses for each each MWh/Mvarh/MVAh.
• The pulse width could be configured once DOs were configured as pulse output, and the two DOs
follow the same setting of pulse length when they are all configured as pulse output.
Manual setting: 10 to 990ms.
Alarm output
Selecting Alarm output, it is mandatory to set up an alarm prior to setting an output as Alarm output. For
alarm settings, please refer to chapter
Always ON/OFF
Selecting Output ON / Output OFF, the output acts as a contact close / contact open.
Selecting Output ON the circuit is closed, selecting Output OFF the circuit is open.
For output connections, please refer to chapter
Communication
Selecting Communication output, the output status is controlled directly via communication bus.
"7.4.Alarms
(ALM)".
"4.3.Wiring
diagrams".