D1M 15 MULTIMETER USER MANUAL
Climatic conditions
Operating temperature
Storage temperature
Relative humidity
Altitude
Pollution degree
Environment
Communication protocol
Modbus RTU
Communication interface
Baud rate
Parity number
Address
Connector
Standards
Power metering and monitoring devices (PMD)
Static meters for AC active energy
Static meters for fundamental component
reactive energy
EMC
Electrical safety
IP degree of protection
-5 to 55°C (K55 IEC61557-12)
-25 to70°C (K55 IEC61557-12)
≤75% yearly average,
≤95% on 30 days/year
≤2km
2
It is prohibited to use in the environment containing
H2S, Cl2, NH3 and other harmful gases
D1M 15 Modbus
RS485 with optical isolation
9.6, 19.2, 38.4, 57.6, 115.2 kbps
Odd (1 stop bit), Even (1 stop bit), None (1 stop bits)
1-247
3 pole terminal
IEC 61557-12
IEC 62053-21
IEC 62053-24
IEC 61326-1