Technical Data - ABB D1M 15 User Manual

Table of Contents

Advertisement

D1M 15 MULTIMETER USER MANUAL

3.5.Technical data

Auxiliary power supply
Voltage range
Frequency
Power Consumption
Installation category
Protection fuse
Measurement accuracy
IEC 61557-12
Active energy
Reactive energy
Active power
Reactive power
Apparent power
Voltage
Current
Frequency
Voltage measurement inputs
Voltage input mode
Voltage Range
Wiring Type
Rated frequency
Protection fuse
VT primary range
VT secondary range
Current measurement inputs
Current input mode
Rated current at secondary side of CT
Rated frequency
Range without accuracy derating
CT primary range
Wiring Type
I/O
Digital Output
Number of channels
Voltage
Current
Width
Mechanical properties
Overall dimensions
IP degree of protection (IEC 60529)
Weight
Fireproof and Heatproof
100-230 V AC/DC ±15%
50 - 60Hz ±5%
5VA max
CAT III 300V class per IEC 61010-1 edition 3
T1 A-277 VAC
IEC 61557-12 PMD/S/K55/1
IEC61557-12 Class 1
IEC 62053-21 Class 1
IEC 61557-12 Class 2
IEC 62053-24 Class 2
IEC 61557-12 Class 1
IEC 61557-12 Class 2
IEC 61557-12 Class 2
IEC 61557-12 Class 0.5
IEC 61557-12 Class 0.5
IEC 61557-12 Class 0.1
Direct or Indirect insertion with VT
80-300 VAC(L-N)
Single-phase, three-phase (3P, 3P+N)
50Hz or 60Hz
T1 A-277 VAC
50~750000V
50~510V
Indirect insertion with CT
1A or 5A
50Hz or 60Hz
50mA-5A AC 120%
1-50000A
Single-phase, three-phase (3P, 3P+N)
2
40V DC
≤60mA DC
10 ~ 990ms
89.0mm x 52.5mm x 63.5mm
Front: IP51 @ IEC 60529
Enclosure: IP20 @ IEC 60529
252g
Terminal 960°C, cover 650°C @IEC 60695-2-1-UL V0
9
9