Siemens 6SL3120-2TE21-0AA3 Manual page 172

Booksize power units
Table of Contents

Advertisement

Internal air cooling
Rated power
Circuit breaker
(IEC 60947 and UL)
Rated short-circuit current
SCCR
3)
Cooling method (internal air cooling)
Max. permissible heat sink
temperature
Sound pressure level
Cooling air requirement
Weight
The specified power ratings apply to the line voltage range from 380 V to 480 V.
1)
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
2)
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
3)
Module in the drive system.
Table 4- 11
Technical data of Active Line Modules
Internal air cooling
Rated power
Infeed
Rated power (S1)
1)
Infeed power (S6 - 40 %)
1)
Peak infeed power
1)
Regenerative feedback
Continuous regenerative power
Peak regenerative power
Supply voltages
Line voltage
Line frequency
Electronics power supply
DC link voltage
Overvoltage trip
Undervoltage trip
2)
Input currents
Rated input current:
for AC 400 V
Input current:
for AC 380 V / AC 480 V
for AC 400 V; S6 - 40 %
for AC 400 V; peak current
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
6SL3130–
7TE21–6AAx
kW
16
See Section Overcurrent protection using line fuses and circuit
breakers (Page 51)
kA
65
Internal fan
° C
85
dB(A)
< 60
m
/h
56
3
Rated voltage for rated data 3 AC 380 V
kg
7
6SL3130–
7TE28–0AAx
kW
80
kW (P
)
80
n
kW (P
)
106
s6
kW (P
)
131
max
kW
80
kW
131
V
3 AC 380 ... 480 ± 10 % (-15 % < 1 min)
ACrms
Hz
47 ... 63
V
24 (20.4 ... 28.8)
DC
V
510 ... 720
DC
V
820 ± 2 %
DC
V
360 ± 2 %
DC
A
122
AC
A
128 / 102
AC
A
161
AC
A
200
AC
Line Modules Booksize
4.2 Active Line Modules with internal air cooling
7TE23–6AAx
7TE25–5AAx
36
55
65
65
Internal fan
Internal fan
90
83
< 65
< 60
112
160
10
17
7TE31–2AAx
120
120
145
175
120
175
182
192 / 152
220
267
7TE25–5AA3 +
Active Interface
Module
55
65
Internal fan
83
< 60
160
17
171

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics s120

Table of Contents