Overcurrent Protection By Means Of Line Fuses And Circuit Breakers - Siemens 6SL3120-2TE21-0AA3 Manual

Booksize power units
Table of Contents

Advertisement

3.3

Overcurrent protection by means of line fuses and circuit breakers

Line fuses or circuit breakers must be used for cable protection/overcurrent protection. NH,
D, and DO type fuses with a gL characteristic or suitable circuit breakers according to
IEC 60947 can be used for this purpose.
Table 3- 1
Recommended line fuses and circuit breakers for Active Line Modules
16 kW
I
fuse
35 A
n
LV HRC line fuse
3NA3 814
Circuit breaker
3RV1031-4FA10
(IEC 60947)
UL-application
Rated current
35 A
Line fuse
AJT35
1)
Circuit breaker
3VL1135-2KM30
Type AJT Class J, source: The Ferraz Shawmut company
1)
Table 3- 2
Recommended line fuses and circuit breakers for Basic Line Modules
I
fuse
n
LV HRC line fuse
Circuit breaker
(IEC 60947)
UL-application
Rated current
Line fuse
1)
Circuit breaker
Type AJT Class J, source: The Ferraz Shawmut company
1)
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
3.3 Overcurrent protection by means of line fuses and circuit breakers
36 kW
80 A
3NA3 824
3RV1041-4LA10
80 A
AJT80
3VL2108-2KN30
20 kW
63 A
3NA3 822
3RV1041-4JA10
60 A
AJT60
3VL2106-2KN30
Line connection and line-side power components
55 kW
80 kW
125 A
160 A
3NA3 132
3NA3 136
3VL2712-1DC33
3VL3720-1DC33
125 A
175 A
AJT125
AJT175
3VL2112-2KN30
3VL3117-2KN30
40 kW
100 A
3NA3 830
3VL2710-1DC33
100 A
AJT100
3VL2110-2KN30
120 kW
250 A
3NA3 144
3VL3725-1DC36
250 A
AJT250
3VL3125-2KN30
100 kW
250 A
3NA3 144
3VL3725-1DC36
250 A
AJT250
3VL3125-2KN30